Week 07

Three-Phase Transformers

I revisit magnetic circuits, transformers, and rotating machines around my transformer report and calculation sheets.

Electrical Machines course visual
Course visual for this study sequence.

What I connect in this unit

Wye and delta connections create different phase-to-line voltage and current relations and impose a phase displacement. Whether three single-phase units form a bank or one three-phase core is used, rating follows line voltage and line current, and connection also determines neutral and harmonic-current paths.

Concept map

  1. Wye and delta connections
  2. Phase displacement
  3. Transformer banks
  4. Rating calculations

Technical anchor

Balanced three-phase rating is S_3phi = sqrt(3) V_LL I_L; in wye, V_phase = V_LL/sqrt(3), while in delta, I_phase = I_L/sqrt(3).

How I review it

Redraw vector-group clock notation with dot polarity as phasors, then verify that phase voltage and current on each winding remain within individual winding ratings.

Connection to the full course

Unit 7 of 12. Unit numbers expand the saved report and calculations into a reading sequence rather than an attendance record.