Term 3-1 · Electrical Engineering Coursework

Power Systems — 765 kV Line & Policy Review

Surge impedance and SIL were recalculated while a non-convergent PowerWorld archive and policy figures were kept in separate evidence classes.

01

765 kV inputs and run status

Surge impedance and SIL were recalculated while a non-convergent PowerWorld archive and policy figures were kept in separate evidence classes.

Status
Zc 255.38 Ω · SIL 2.292 GW · PWB rerun: Blackout
Evidence
Source-Derived · Independent Recalculation · PowerWorld 24 Tool Rerun
Contribution
Team Project · Individual contribution unconfirmed
02

Line calculations versus power-flow output

The core engineering task is evidence separation: reproducible line arithmetic, a solver-divergence archive, and policy figures must not be collapsed into one result. The line values were independently recalculated; divergence is retained only as debugging evidence.

  • Lossless Zc and SIL use 765 kV, 350 km, z=j0.3 Ω/km, and y=j4.6 µS/km.
  • Independent results are Zc≈255.38 Ω, SIL≈2.292 GW, and current≈1.729 kA.
  • Non-physical per-unit voltages and blackout state are not interpreted as real-grid performance.
  • PowerWorld 24 reran the saved 2214 MW `newcase.pwb` state and reproduced Blackout.
  • 2038 demand, peak, and capacity figures retain their report/source context.
03

Zc, SIL, and demand values

04

PowerWorld model views

Source result views excluding student identifiers, personal data, local paths, and third-party teaching material.

05

Transmission-line recalculation

06

Calculated values and solver state

Voltage / length765 kV / 350 km
Surge impedance255.38 Ω
SIL2.292 GW
SIL current1.729 kA
PowerWorld 24 rerun2214 MW → Blackout
2038 energy735.1 → 624.5 TWh
2038 peak145.6 → 129.3 GW
07

Blackout diagnosis versus report values

The PowerWorld 24 rerun confirms a Blackout diagnostic for the saved 2214 MW state; it does not validate the report's 3000/3100/3200 MW stages or 5380 MW compensated case. Dynamic stability, protection, N-1, and production-grid validation are not claimed. Personal identifiers in the GUI are withheld.

Calculation code and PowerWorld run record